 Voltage Sensitive Relays
WILMARTM Protective Relays - 250 Series, Over/Undervoltage
Function: 27/59
* ANSI/IEEE C37.90-1978
The 250 series relays provide combined Overvoltage and Undervoltage protection in a single compact unit.
6 -32 STUDS (6)
Models are available for single phase or three phase applications, and are suitable for either 50 Hz, 60 Hz, or 400 Hz operation. The trip point is adjustable. A transistorized circuit provides a sharp and accurate response at the preset tripping voltage; unaffected by temperature or frequency variations.
2
Single Phase
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Part Number
Nominal Voltage ............................... Undervoltage Trip ............................ Overvoltage Trip ............................... Pick-Up to Drop-Out Differential ..... Contact Ratings ................................ Contact Form .................................... Operating Temperature Range ........
Notes: 1. Remove screws for access the overvoltage or undervoltage trip adjustments. Clockwise rotation of the adjustment potentiometer will raise the trip point.
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
3.5 00
3
7 /8
3
B.C .
.C. 0B .75 2 00 3.5
/64" DIA. 4 MTG. HOLES
13
Three Phase
Contact Arrangements
NC - Open at nominal voltage. Closed at Overvoltage and Undervoltage N O - Closed at nominal voltage. Open at Overvoltage and Undervoltage PRODUCT SPECIFICATIONS PART NUMBER SELECTION
Sample Part No. 250X
250 Series
See Part Number Selection 70-100% of nominal voltage, screwdriver adjustable 100-125% of nominal voltage, screwdriver adjustable 3% maximum 5 amp resistive at 120 VAC or 28 VDC One set N.O., one set N.C. -20C to +85C
Model: L-L Volts 250X = 120 VAC, 1 Phase, 50-400 Hz 251X = 120/208 VAC, 3 Phase, 4 Wire, 50-400 Hz 252X = 115 VAC, 3 Phase, 3 Wire, 50-400 Hz 253X* = 230 VAC, 3 Phase, 3 Wire, 50-400 Hz 254X* = 380 VAC, 3 Phase, 3 Wire, 50-400 Hz 255X*= 460 VAC, 3 Phase, 3 Wire, 50-400 Hz 256X* = 575 VAC, 3 Phase, 3 Wire, 50-400 Hz Mounting Blank = Stud X = Flange
* Enclosure heigth is 3.835"
Consult factory for additional models.
25


▲Up To Search▲   

 
Price & Availability of 256X

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X